4.2 Alarm Indications: When an overtemperature or
undertemperature condition exists in any zone occupied by
an IMP controller, both audio (tones) and visual (LED)
alarms will occur in the SAM.
a. Over Temp. : Occurs when an IMP thermocouple is 30
deg F (17 deg C) or more above setpoint. The speaker will
emit a higher pitched audio tone of about 2 KHz repeating
about twice per second. At the same time, the over temper-
ature LED will flash, and relay closure will occur.
b.Under Temp.: Occurs when an IMP-15 thermocouple is
30 deg F (17 deg C) or more below setpoint. The speaker
will emit a lower pitched audio tone of about 1 KHz repeat-
ing about once per second. At the same time, the under-
temperature LED will flash, and relay closure will occur.
c. Over Temp. Alarm Priority: If an overtemperature and
undertemperature condition exist simultaneously from
more than one IMP controller, SAM will indicate only the
overtemperature condition. SAM will not recognize any
undertemperature condition, until all overtemperature
alarms have been cleared.
4.3 Front Panel Output Connector: A set of relay contacts are
available at this connector for use with external equipment if
desired. Observe the 5 amp maximum contact rating. Pins 1
and 2 have normally closed (N.C.) contacts. Pins 1 and 3 have
normally opened (N.O.) contacts.
a. During either an over-or under-temperature alarm condi-
tion, the relay will be energized.
b. Relay operation is defeated when the Low Temperature
Alarm mode switch is in the Inhibit ( ) position. (This will
be clarified in the next section.)