3- Thermocouple open or reversed:
If any TC fault is detected during closed-loop operation,
the output power will be cut off. If it is necessary to
apply power to the load during a TC fault condition,
the controller can be switched to manualmode. The
output power will be a function of the manual control
knob setting. Since the controller is now operating in
open-loop mode, extreme care must be taken when
adjusting to prevent excess output power which would
overheat the load.
4- No heatfault:
The IMP series controller has included in its
microprocessor a program which detects that the
temperature is not rising as it should in response to full
power output. “No Heat” is defined as the condition
under which the temperature does not increase more
than 2 degrees F during a 60-second interval during
start-up. It takes 60 seconds to detect “No Heat” when
power is first turned on in closed-loop mode, and longer
if CompuStep is active.
In the beginning of the CompuStep mode, only a small
amount of power is applied to the load and the rate of
temperature rise could be less than 2 degrees F (1°C) in
60 seconds. In order to compensate for this, the test is
not performed until one minute after power is turned
on. By that time, enough power is being applied to the
load to sustain the rate of 2 degrees F (1°C) in 60 sec-
onds. It takes 1 minute, 60 seconds to detect “No
Heat” in CompuStep mode when power is first turned
on. When “No Heat” alarm is detected, output power is
cut off.