What to do:
A. Try resetting the controller by turning its AC power OFF and
then ON.
B. If “No Heat” persists, then the problem could be one of the
following.
a- Open heater or load.
b- Thermocouple shorted. Switch to manual mode to
override this condition.
c- Load circuit open. This can be caused by an open power
cable, an open connector or a failed triac in the
controller. Exchange the module with a known good
module to eliminate suspect triac or module.
d- Slow heater. Use higher power heater or operate in
manual mode until setpoint is achieved.
e- Thermocouple too far away from heat source which
causes less than 2 degrees F (1°C) rise in 60 seconds due
to thermal lag. Move thermocouple as close to heater as
possible or use heater with built in thermocouple.
f- To defeat “No Heat” circuit, if not used or required,
remove jumper J4 and that circuit will no longer be
active.
User’s Selected Jumper Option
1- For degree Celsius operation,
install jumper on PC board marked J1
2- For 50 Hz operation
install jumper on PC board marked J2
Since the microprocessor reads the status of the jumpers during
power up, the power has to be turned off and on again in order to
activate the jumper function.
13