7.2 Read Status
Function 07 (Read Status) returns an eight bit status with the following
meanings:
Bit Address Variable
1 (LSB) 1 -
2 2 -
3 3 -
4 4 Main output condition (0 = OFF, 1 = ON)
5 5 AL2 alarm status (0 = OFF, 1 = ON)
6 6 AL3 alarm status (0 = OFF, 1 = ON)
7 7 Out of range (0 = Normal operation, 1 = Safety)
8 (MSB) 8 Auto-Tune (0 = OFF, 1 = Run)
7.3 Word Zone - Page 1 Parameters
Address
Modbus JbuS Variable Parameter
Code
Type
0 1 Process variable R
1 2 Setpoint R/W
1
2 3 Main output R
3 4 Target Setpoint R
4 5 Local Setpoint R/W
2
5 6 Proportional Band (Hysteresis ON - OFF)
3
P.b. (hy))
R/W
6 7 Overshoot control
O.C.
R/W
7 8 Integral time
t.i.
R/W
8 9 Derivative time
t.d.
R/W
9 10 Output cycling time
t.c.
R/W
10 11 Low range
Sc.Lo
R
11 12 High range
Sc.Hi
R
12 13 AL2 Alarm threshold
A2S.P
R/W
13 14 AL3 Alarm threshold
A3S.P
R/W
14 15 AL2 Alarm Hysteresis
A2hy
R/W
15 16 AL3 Alarm Hysteresis
A3hy
R/W
16 .. 28 17 .. 29 - - -
29 30 Setpoint low limit
S.P. L
R/W
30 31 Setpoint high limit
S.P. H
R/W
31 32 - - -
32 33 Main output high limit
OP. H
R/W
33 34 - - -
34 35 Setpoint ramp up
Sl. u
R/W
35 36 Setpoint ramp down
Sl. d
R/W
36 37 Input filter
t.FiL
R/W
37 38 Input shift
In.Sh
R/W
38 39 Auto-Tune enable
tune
R/W
39 40 - - -
40 41 Serial comm.s address
Addr
R/W
41 42 - - -
42 43 Retransmission low range
rt.Lo
R/W
43 44 Retransmission high range
rt.Hi
R/W
44 .. 99 45 .. 100 - - -